FJ6/ Bare Copper Terminal Bars | HAIYAN

FJ6/ Bare Copper Terminal Bars

Product Features 

  • One-piece bare copper bar design without insulated base
  • All connection points electrically common (busbar function)
  • High electrical conductivity with low contact resistance
  • Requires external insulation or protected installation
  • Suitable for internal grounding and busbar applications

Detailed introduction

Application

Suitable for neutral (N) and protective earth (PE) busbar applications in low-voltage electrical distribution systems.

Designed for current collection and equipotential connection in distribution boards,control panels, and switchgear assemblies.

Key Specifications

6-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 6*25 mm²
External dimensions (total length): 124 mm
Copper strip size:15.5*20.5(mm)
Order Number: 210896
9-way
InputConductorRange 10-50 mm²
OutputConductorRange: 9*25 mm²
External dimensions (total length): 146 mm
Copper strip size:15.5*20.5(mm)
Order Number: 210897
12-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 12*25 mm²
External dimensions (total length): 172 mm
Copper strip size:15.5*20.5(mm)
Order Number: 210898
16-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 16*25 mm²
External dimensions (total length): 205 mm
Copper strip size:15.5*20.5(mm)
Order Number: 210899
18-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 18*25 mm²
External dimensions (total length): 223 mm
Copper strip size:15.5*20.5(mm)
Order Number: 210900
9-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 9*16 mm²
External dimensions (total length): 168 mm
Copper strip size:10*18(mm)
Order Number: 210901
12-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 12*16 mm²
External dimensions (total length): 183 mm
Copper strip size:10*18(mm)
Order Number: 210902
15-way
InputConductorRange: 10-50 mm²
OutputConductorRange: 15*16 mm²
External dimensions (total length): 215 mm
Copper strip size:10*18(mm)
Order Number: 210903

Installation and Operation

  • Fixed mounting onto mounting plates or insulated supports using screws.
  • Ensure appropriate insulation measures before operation.

Reference Table for Copper Conductors for Incoming and Outgoing Lines