FJ6/HYJ Series Branch Type Insulation Piercing Connector — Flame-retardant Version(1kV) | HAIYAN

FJ6/HYJ Series Branch Type Insulation Piercing Connector — Flame-retardant Version(1kV)

Product features

  • Optional flame-retardant version available for ZR/NH cables requiring higher fire-safety performance.
  • All components are flame-retardant and compliant with 960°C glow-wire and vertical burning tests.
  • Connector body made of high-strength, flame-retardant insulating material resistant to mechanical and climatic stress.
  • Waterproof construction withstands 1 kV insulation test under water without breakdown.
  • Sealed branch end-cap prevents moisture ingress.
  • Suitable for live-line or de-energized installation.

Detailed introduction

Application

The FJ6/HYJ Series insulation piercing connectors are used for the connection, branching, and earthing of overhead insulated conductors.They are suitable for 10 kV lines and 1 kV systems (the product in this link is designed for 1 kV applications).

Key Specifications

FJ6/HYJ/V0-35
Main Conductor Range (Input):  1.5–35 mm²
Branch Conductor Range (Output):  1.5–10 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  63 A
Overall Dimensions:  27 × 41 × 62 mm
Order Number:  212580
FJ6/HYJ1/V0-95
Main Conductor Range (Input):  16-95 mm²
Branch Conductor Range (Output):  1.5–10 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  75 A
Overall Dimensions:  27 × 41 × 62 mm
Order Number:  212581
FJ6/HTD2/V0-95
Main Conductor Range (Input):  16-95 mm²
Branch Conductor Range (Output):  4–35(50) mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  138 A
Overall Dimensions:  46 × 52 × 87 mm
Order Number:  212582
FJ6/HTD2/V0-150
Main Conductor Range (Input):  50-150 mm²
Branch Conductor Range (Output):  6-35(50) mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  140 A
Overall Dimensions:  46 × 52 × 87 mm
Order Number:  212583
FJ6/HYJ3/V0-95
Main Conductor Range (Input):  25-95 mm²
Branch Conductor Range (Output):  25-95 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current: 214 A
Overall Dimensions:  52 × 61 × 95 mm
Order Number:  212584
FJ6/HYJ3/V0-120
Main Conductor Range (Input):  16-120 mm²
Branch Conductor Range (Output):  16-120 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  299 A
Overall Dimensions:  52 × 61 × 95 mm
Order Number:  212585
FJ6/HYJ3/V0-150
Main Conductor Range (Input):  35-150 mm²
Branch Conductor Range (Output):  35-150 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  316 A
Overall Dimensions:  52 × 61 × 95 mm
Order Number:  212586
FJ6/HYJ4/V0-185
Main Conductor Range (Input):  70-185 mm²
Branch Conductor Range (Output):  25-95 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  276 A
Overall Dimensions:  52 × 68 × 100 mm
Order Number:  212587
FJ6/HYJ4/V0-240
Main Conductor Range (Input):  120-240 mm²
Branch Conductor Range (Output):  25-120(150) mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  399 A
Overall Dimensions:  52 × 68 × 100 mm
Order Number:  212588
FJ6/HYJ/V0-300
Main Conductor Range (Input): 150-300 mm²
Branch Conductor Range (Output):  6-35 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  420 A
Overall Dimensions:  52 × 68 × 100 mm
Order Number:  212591
FJ6/HYJ5/V0-185
Main Conductor Range (Input):  70-185 mm²
Branch Conductor Range (Output):  6-35 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  275 A
Overall Dimensions:  52 × 68 × 100 mm
Order Number:  212589
FJ6/HYJ/V0-240
Main Conductor Range (Input):  120-240 mm²
Branch Conductor Range (Output):  6-35 mm²
Bolt Quantity:  1 pc
Applicable Voltage:  1 kV
Nominal Current:  395 A
Overall Dimensions:  52 × 68 × 100 mm
Order Number:  212590

Installation and Operation

  • Install and secure the main feeder cable using standard methods.
  • Remove approx. 0.6 m of the outer sheath at the branching position without damaging the phase insulation.
  • Select a branch cable ≤ 3 m and strip the sheath at both ends.
  • Install the branch connectors sequentially along the exposed section, keeping >10 cm spacing between units.