FJ6/TTD Series Branch Type Insulation Piercing Connector(1kV) | HAIYAN

FJ6/TTD Series Branch Type Insulation Piercing Connector(1kV)

Typical applications include:

  • Branching of building distribution insulated cables
  • LV overhead insulated conductor connections
  • Residential/commercial service entry branching
  • Street lighting distribution networks
  • Urban and rural network insulation retrofit projects

Product Features

  • No-strip installation: branching can be made at any point along the main conductor without cutting or removing insulation.
  • Constant piercing pressure ensured by shear-head bolts, providing secure electrical contact and safe, reliable tapping.
  • High-strength insulating body resistant to mechanical stress, vibration, climatic aging, and UV exposure.
  • Waterproof performance: withstands 6 kV under submerged conditions with no breakdown.
  • Corrosion-resistant bolts and hardware ensure long-term outdoor performance.
  • Fully sealed construction with a waterproof branch end-cap; end-cap can be placed on the left or right side as needed.
  • Applicable to insulated copper or aluminum conductors.
  • Cost-effective installation: reduces required space, eliminates junction boxes, and avoids cable return routing in building applications.

 

Detailed introduction

Application

The TTD series insulation piercing connectors are used for the branching of insulated conductors in building distribution systems, low-voltage overhead networks, service entry cables, and street lighting circuits.

They support both live-line and de-energized installation and are suitable for insulated copper or aluminum conductors.

Key Specifications

FJ6/TTD041FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 6-35 mm²
Branch Conductor Range (Output): 1.5-10 mm²
Nominal Current: 86A
Torque Nut: F1309
Bolt Quantity: 1*M8(13)
Order Number: 212614
FJ6/TTD051FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 16-95 mm²
Branch Conductor Range (Output): 1.5-10 mm²
Nominal Current: 86A
Torque Nut: F1309
Bolt Quantity: 1*M8(13)
Order Number: 212615
FJ6/TTD101FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 6-50 mm²
Branch Conductor Range (Output): (2.5)6-35 mm²
Nominal Current: 200A
Torque Nut: F1309
Bolt Quantity: 1*M8(13)
Order Number: 212616
FJ6/TTD121FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 25-95 mm²
Branch Conductor Range (Output): 2.5-25 mm²
Nominal Current: 161A
Torque Nut: F1309
Bolt Quantity: 1*M8(13)
Order Number: 212617
FJ6/TTD151FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 25-95 mm²
Branch Conductor Range (Output): (2.5)6-25 mm²
Nominal Current: 200A
Torque Nut: F1318
Bolt Quantity: 1*M8(13)
Order Number: 212618
FJ6/TTD201FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 35-95 mm²
Branch Conductor Range (Output): 25-95 mm²
Nominal Current: 377A
Torque Nut: F1318
Bolt Quantity: 1*M8(13)
Order Number: 212619
FJ6/TTD211FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 35-95 mm²
Branch Conductor Range (Output): 16-70 mm²
Nominal Current: 310A
Torque Nut: F1318
Bolt Quantity: 1*M8(13)
Order Number: 212620
FJ6/TTD231FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 25-95 mm²
Branch Conductor Range (Output): 10-50 mm²
Nominal Current: 242A
Torque Nut: F1314
Bolt Quantity: 1*M8(13)
Order Number: 212621
FJ6/TTD241FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 50-150 mm²
Branch Conductor Range (Output): (2.5)6-35 mm²
Nominal Current: 200A
Torque Nut: F1314
Bolt Quantity: 1*M8(13)
Order Number: 212622
FJ6/TTD251FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 50-150 mm²
Branch Conductor Range (Output): 25-95 mm²
Nominal Current: 377A
Torque Nut: F1314
Bolt Quantity: 1*M8(13)
Order Number: 212623
FJ6/TTD271FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 35-120 mm²
Branch Conductor Range (Output): 35-120 mm²
Nominal Current: 437A
Torque Nut: F1318
Bolt Quantity: 1*M8(13)
Order Number: 212624
FJ6/TTD281FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 50-185 mm²
Branch Conductor Range (Output): (2.5)6-35 mm²
Nominal Current: 200A
Torque Nut: F1314
Bolt Quantity: 1*M8(13)
Order Number: 212625
FJ6/TTD301FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 25-95 mm²
Branch Conductor Range (Output): 25-95 mm²
Nominal Current: 377A
Torque Nut: F1314
Bolt Quantity: 1*M8(13)
Order Number: 212626
FJ6/TTD401FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 50-185 mm²
Branch Conductor Range (Output): 50-150 mm²
Nominal Current: 504A
Torque Nut: F1318
Bolt Quantity: 2*M8(13)
Order Number: 212627
FJ6/TTD431FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 70-240 mm²
Branch Conductor Range (Output): 16-95 mm²
Nominal Current: 377A
Torque Nut: F1720
Bolt Quantity: 2*M10(17)
Order Number: 212628
FJ6/TTD441FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 95-240 mm²
Branch Conductor Range (Output): 50-150 mm²
Nominal Current: 504A
Torque Nut: F1725
Bolt Quantity: 2*M10(17)
Order Number: 212629
FJ6/TTD451FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 95-240 mm²
Branch Conductor Range (Output): 95-240 mm²
Nominal Current: 530A
Torque Nut: F1725
Bolt Quantity: 2*M10(17)
Order Number: 212630
FJ6/TTD551FJ
Applicable Voltage: 1 kV
Main Conductor Range (Input): 120-400 mm²
Branch Conductor Range (Output): 95-240 mm²
Nominal Current: 679A
Torque Nut: F1737
Bolt Quantity: 2*M10(17)
Order Number: 212631

Installation and Operation

  • Verify that the connector model matches the conductor size prior to installation.
  • Suitable for single-layer insulated conductors; the connector may be removed but must not be reused.
  • Conductors shall be clean and free from damage; preheat insulation if ambient temperature is below –10 °C.
  • Adjust the branch end-cap position according to the branch cable insertion direction.
  • Insert the branch conductor fully into the end-cap until it engages the internal sealing element.
  • Position the connector at the tapping point on the main conductor and hand-tighten the top nut to secure it in place.
  • Tighten the shear-head bolt using a socket wrench only; for dual-bolt models, tighten alternately.
  • Continue tightening until the shear-head breaks off, indicating correct torque has been achieved. Supporting the lower body with a secondary wrench will reduce installation effort.